January 23rd | 3200 Sample Blvd., Tulsa, OK 74104
Prepared by Drew Sleezer
LIC 70001227
Date: 7/26/2021 | Time: 09:00 AM | Report ID: |
Property: 1234 Commercial St Tulsa OK |
Customer: Sample Report |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Any pictures included in the report are intended to represent the issue. Pictures are not intended to show all areas of concern.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Any pictures included in the report are intended to represent the issue and are not intended to show all areas of concern.
In Attendance: Listing agent, Customer | Type of building: Commercial event center | Temperature: Over 65 (F) = 18 (C) |
Weather: Cloudy | Ground/Soil surface condition: Dry | Radon Test: No |
Water Test: No |
|
Styles & Materials
Roof Covering: Rubber membrane Viewed roof covering from: Walked roof |
|
Styles & Materials
Siding Material: Brick veneer Extra Info : tile Driveway: Parking lot |
.
|
Styles & Materials
Ceiling Materials: Gypsum Board Wall Material: Gypsum Board Interior Doors: Wood Window Types: Thermal/Insulated |
|
Styles & Materials
Foundation: Poured concrete Method used to observe Crawlspace: No crawlspace Floor Structure: Slab Wall Structure: Wood Roof Structure: Engineered wood trusses Roof-Type: Gable Flat Method used to observe attic: Walked Limited Access |
|
Styles & Materials
Plumbing Water Distribution (inside building): PEX Plumbing Waste: PVC Water Heater Power Source: Gas (quick recovery) |
|
Styles & Materials
Electrical Service Conductors: Below ground Panel Type: Circuit breakers Branch wire 15 and 20 AMP: Copper Wiring Methods: Romex |
|
Styles & Materials
Heat Type: Forced Air Energy Source: Gas Ductwork: Insulated Filter Type: Disposable Types of Fireplaces: None Cooling Equipment Type: Air conditioner unit Cooling Equipment Energy Source: Electricity |
|
Styles & Materials
Attic Insulation: Batt Ventilation: None found |
|
9548 E. 108th St. S.
Tulsa, OK 74133
918-853-5113
Customer
Sample Report
Address
1234 Commercial St
Tulsa OK
1.2 | Skylights, Chimneys and Roof Penetrations | |
Repair or Replace | ||
Roof vent installation may allow moisture intrusion to occur. I recommend qualified contractor repair or replace as needed.
|
1.3 | Roof Drainage Systems | |
Repair or Replace | ||
(1) The exterior downspouts discharge water at the foundation. I recommend improvement of the drain downspouts so water is properly carried away from
the structure.
|
||
(2) Water is leaking from the upper portion of the left side downspout. This is allowing water to run down the wall. I recommend qualified contractor repair or
replace as needed.
|
2.0 | Wall Cladding, Trim, Soffits, and Fascia | |
Repair or Replace | ||
(1) Separations in the tile at the front and rear of the building. It appears some of the tile is loose. Gaps will allow moisture intrusion. I recommend qualified
contractor repair or replace as needed.
|
||
(2) Paint peeling at the pergolas. I recommend qualified contractor prep and paint as needed to prevent deterioration.
|
||
(3) Wasp nests at the rear of the building should be removed.
|
||
(4) Gap between the cap and the wall at the rear of the building. Loose/deteriorated membrane. This will allow moisture intrusion into the wall assembly. I
recommend qualified contractor repair or replace as needed.
. |
2.1 | Doors (Exterior) | |
Repair or Replace | ||
(1) Broken door stop at the left front exterior door. I recommend qualified contractor repair or replace as needed.
|
||
(2) The left side center and right rear exit doors are not closing properly. I recommend qualified contractor repair or replace as needed.
|
||
(3) The right front door did not close fully when tested. I recommend qualified contractor repair or replace as needed.
|
2.3 | Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings | |
Repair or Replace | ||
No handrail at the right rear steps. Potential safety concern. I recommend installation of a handrail for safety.
|
2.4 | Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building) | |
Repair or Replace | ||
(1) Parking lot markings and designations are deteriorated and unreadable in some areas. Re-marking may be desired.
|
||
(2) Damage at the entry drive. I recommend qualified contractor repair or replace as needed.
|
||
(3) There is evidence of water pooling/inadequate drainage at some areas of the parking lot. Deterioration may occur if not corrected. I recommend qualified
contractor repair or replace as needed.
|
||
(4) Some of the vegetation is overgrown/damaged.
|
||
(5) Vegetation in contact with structure should be trimmed back.
|
||
(6) Unevenness at the rear walkway brick. This is a potential trip hazard/safety concern. I recommend qualified
contractor repair or replace as needed.
|
||
(7) There is a insufficient slope at the exterior of the building on the left side. This can cause or contribute to water
intrusion or deterioration. I recommend correcting landscape or adding drains to drain water away from home.
|
2.5 | Other | |
Repair or Replace | ||
Damaged bench at the right side courtyard. This is a safety concern. I recommend repair or removal.
|
4.0 | Ceilings, walls, and trim | |
Repair or Replace | ||
(1) Stain on the ceiling of the roof access ladder hallway. Moisture was found at the time of inspection. I recommend qualified contractor determine the
source of the moisture and repair or replace as needed.
|
||
(2) There is cracking at some areas of the interior drywall. Repair may be desired.
|
||
(3) Damaged trim at the left side entry chair storage area. I recommend qualified contractor repair or replace as needed.
|
||
(4) Stain on the ceiling of the center hallway left front closet. No moisture was found at the time of inspection. I recommend qualified contractor determine
if leak is present and repair or replace as needed.
|
||
(5) Damaged sheetrock, indication of possible previous moisture at the center hallway left rear office. No moisture was found at the time of inspection. I
recommend consulting the seller to determine if repairs were made. I recommend qualified contractor determine if leak is present and repair or replace
as needed.
|
||
(6) Stains on the ceiling of the men's bathroom. No moisture was found at the time of inspection. I recommend qualified contractor determine if leak is
present and repair or replace as needed.
|
4.3 | Counters and Cabinets (representative number) | |
Repair or Replace | ||
Broken hinge at the left rear AV closet. I recommend qualified contractor repair or replace as needed.
|
4.4 | Doors and Windows (representative number) | |
Repair or Replace | ||
(1) Broken door stop at the left side entry chair storage area. I recommend qualified contractor repair or replace as needed.
|
||
(2) The right rear kitchen area door is not closing properly. I recommend qualified contractor repair or replace as needed.
|
||
(3) The men's bathroom door stop is loose. I recommend preventative repair to prevent damage.
|
||
(4) Cloudy window (failed seal) at the right rear kitchen area. Further deterioration may occur if not repaired. A qualified contractor should repair or replace
as needed.
|
4.5 | Other | |
Repair or Replace | ||
(1) Fire extinguishers and fire suppression system inspection dates are not current. I recommend inspection and evaluation by a qualified company for fire
safety and compliance.
|
||
(2) Fire alarm activation/pull is obstructed by property. This should be accessible at all times for safety. I recommend property be moved and clearance
maintained for safety.
|
||
(3) Fire suppression system sprayer cover missing at the left side hallway center room. I recommend qualified contractor repair or replace as needed.
|
5.1 | Ceilings, Floors, Walls (Structural) | |
Repair or Replace | ||
Crack at the floors in the front storage room. Indication of structural movement. I recommend evaluation by structural engineer. I recommend qualified
contractor repair or replace as needed.
|
6.0 | Plumbing Drain, Waste and Vent Systems | |
Repair or Replace | ||
(1) Sink drain plumbing is not properly aligned with the floor drain. This is causing deterioration at the tile and grout. I recommend qualified contractor
repair or replace as needed.
|
||
(2) The right rear kitchen area sink drain is leaking. I recommend qualified contractor repair or replace as needed.
|
6.1 | Plumbing Water Supply, Distribution System and Fixtures | |
Repair or Replace | ||
(1) Damaged sprinkler line observed at the left side of the front entry. I recommend qualified contractor repair or replace as needed.
|
||
(2) The women's bathroom right sink, the family bathroom sink, and the men's left sink faucets would not turn on. I recommend qualified contractor repair or
replace as needed.
|
||
(3) The family bathroom toilet is running continuously. I recommend qualified contractor repair or replace as needed.
|
||
(4) The automatic flush sensors did not operate properly when tested at the men's urinals. I recommend qualified contractor repair or replace as needed.
|
||
(5) Leak at the right rear wash sink spout. I recommend qualified contractor repair or replace as needed.
The sink fixture is loose at the wall. I recommend qualified contractor repair or replace as needed. |
||
(6) Hot water circulation pump is turned off/not operating. I recommend qualified contractor repair or replace as needed.
|
||
(7) The pex pipe does not have proper clearance from the vent per the manufacturer. I recommend repair by licensed plumber.
|
||
(8) The private women's room bathroom toilet would not flush. Flapper chain is broken. I recommend qualified contractor repair or replace as needed.
|
||
(9) The women's room toilet ran continuously after being flushed. I recommend qualified contractor repair or replace as needed.
|
7.1 | Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels | |
Repair or Replace | ||
Area in front of the electrical panels should be kept clear for proper access. I recommend property not be stored in this area.
|
7.2 | Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage | |
Repair or Replace | ||
Extension cords used as permanent wire at the entry left side chair storage area, the left rear chair storage area, the center hallway left rear office, and
the av closets. Proper wire should be installed or extension cords removed. I recommend repair or replace by qualified contractor.
|
7.3 | Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) | |
Repair or Replace | ||
(1) Missing fixture/open junction at the women's bathroom. I recommend qualified contractor repair or replace as needed.
|
||
(2) One of the men's bathroom lights did not work when tested. I recommend qualified contractor repair or replace as needed.
|
||
(3) Many of the light fixtures in the right side great room did not work when tested. Try bulbs first. I recommend qualified contractor repair or replace as
needed.
|
||
(4) Multiple exterior lights did not work when tested. I recommend qualified contractor repair or replace as needed.
|
||
(5) Outlet loose to the wall at the private women's bathroom. I recommend qualified contractor repair or replace as needed.
|
||
(6) Several light switches did not work when tested. Some lights could not be turned off. I recommend qualified contractor repair or replace as needed.
|
7.4 | Operation of GFCI (Ground Fault Circuit Interrupters) | |
Repair or Replace | ||
(1) Multiple GFCIS not working properly at exterior of the building. I recommend qualified contractor repair to normal working order for safety.
|
||
(2) Front right side GFCI is loose at the wall. I recommend qualified contractor repair or replace as needed.
|
||
(3) Right side rear pergola GFCI is partially buried. I recommend qualified contractor repair or replace as needed.
|
8.0 | Heating Equipment | |
Repair or Replace | ||
(2) The right front great room HVAC unit did not work when tested. I recommend qualified contractor repair or replace as needed.
|
8.1 | Heat and Air Operating and Safety Controls | |
Repair or Replace | ||
Thermostat face is loose at the rear of the great room. I recommend qualified contractor repair or replace as needed.
|
8.2 | Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) | |
Repair or Replace | ||
(1) Several air intake filters are not properly installed. I recommend qualified contractor repair or replace as needed.
|
||
(2) The Filter(s) dirty. This is a maintenance issue. I recommend qualified person install new filters as needed.
The filters are located at the HVAC units on the roof. |
||
(3) Disconnected/damaged duct pipe with signs of previous moisture in the attic space near the roof access. No moisture was found at the time of
inspection. I recommend qualified contractor determine if leak is present and repair or replace as needed. I recommend duct work be repaired/replaced
by qualified contractor as needed.
|
8.5 | Cooling and Air Handler Equipment | |
Repair or Replace | ||
(1) HVAC condensate is draining onto the roof surface. This may allow deterioration to occur over time. I recommend qualified contractor repair or replace
as needed.
|
||
(3) The right front great room front AC unit did not work when tested. I recommend qualified contractor repair or replace as needed.
|
||
(4) The right side rear great room AC unit did not produce proper temperature differential when tested. I recommend qualified contractor repair or replace as
needed.
|
9.0 | Insulation in attic and walls | |
Repair or Replace | ||
Insulation is installed with "paper or kraft" face out. This is generally not recommended by the manufacturer due to condensation issues and fire safety.
A qualified contractor should repair or replace as needed.
Insulation is missing in several places in attic. Heat loss can occur more on this home than one that is properly insulated. A qualified contractor should repair or replace as needed. |
13.0 | Sprinkler Operation | |
Repair or Replace | ||
Sprinkler system did not work when tested. System valve appears to be turned off. I recommend qualified contractor restore service and test the system
for proper operation.
Sprinkler controller is unplugged/turned off. |